PMI-8I
multi counters module 101 x 22,5 mm
 
              
            
          Multi counters module PMI-8I allows to counting
 of pulses delivered to 8 isolated binary inputs
 independently. All counters are 32 bit long and 
can be read and cleared by user at any time. 
Occurrence of HIGH state on particular input is 
signalled by green LEDs marked IN1 to IN8. 
Incrementation of counter occurs after falling
 edge on particular input (input state changes
 from HIGH to LOW). It is essential that pulses 
have fulfill some time restrictions. These 
restrictions depend on settings of implemented
 internal digital filter, which allows to eliminate
 signal oscillations corresponding to contacts
 bouncing (of mechanical sensors). Standard
 functions of MODBUS RTU protocol make
 internal registers (like: address, device ID,
 counters content etc.) accessible via RS-485 
interface. All PMI-8I operating functions, 
available via the RS-485, can be implemented 
from any typical visualization software or, for
 instance, with a suitably PAC-99X controller.
Features
- multi counters module
- 8 independent voltage inputs
- LEDs for module operation and Modbus transmission signalling
- interface RS-485/Modbus RTU
Accessories
Functionality:
- galvanic separation of the digital inputs from the module supply voltages,
- internal digital filter,
- signalling MODBUS correct operation and transmission,
- input signals connected by means of the socket-plug connectors,
- signalling of inputs states.


 
  
 